ABB REF615 (Type Code: HBFDACADNAA1BCN1XE) Feeder Protection and Control Relay

ABB REF615 (Type Code: HBFDACADNAA1BCN1XE) Feeder Protection and Control Relay

1. Rated & Electrical Parameters

System Voltage: 6–36 kV

Frequency: 50 / 60 Hz

Current Input: 3×Ia, Ib, Ic + Io (Selectable 1 A or 5 A)

Voltage Input: 3×Ua, Ub, Uc (Rated 100/110 V)

Auxiliary Power Supply

AC: 100–240 V (38…110% Un)

DC: 24–250 V (80…120% Un)

Power Consumption: Standby < 8.4 W / Operating < 13 W

2. Protection Functions (ANSI Codes)

Phase Overcurrent: 51P (Long Time Delay), 50P-1/2/3 (Instantaneous/High-set)

Neutral / Earth Overcurrent: 51N/50N, 51G/50G, 50SEF (Sensitive Earth Fault)

Negative Sequence Overcurrent: 46-1/46-2 (Unbalance / Phase Loss)

Thermal Overload: 49F; Cold Load Pickup: 62CLD

Circuit Breaker Failure: 50BF; Arc Flash Protection: AFD (Optional)

Others: High Impedance Fault (HIZ), Phase Disconnection 46PD, Auto Reclosing 79

3. Communication Interfaces & Protocols

Ethernet: 2 × 10/100 Mbps RJ45 (IEC 61850 MMS/GOOSE)

Serial Port: 1 × RS-485 (Modbus RTU)

Protocols: IEC 61850 (with GOOSE < 10 ms), Modbus, DNP3.0, IEC 60870-5-103

Time Synchronization: SNTP, IRIG-B (Resolution: 1 ms)

Redundancy: PRP / HSR (Optional)

Category:

Description

ABB REF615 (Part Code: HBFDACADNAA1BCN1XE) Feeder Protection and Control Relay

1. Product Overview

Full Model: REF615 HBFDACADNAA1BCN1XE (IEC-compliant Feeder IED of Relion®615 Series)

As a member of ABB Relion615 intelligent protection & control product line, it is an integrated protection and control IED dedicated to medium-voltage 10kV~35kV distribution feeders. It applies to urban power grids, industrial substations, auxiliary power outgoing feeders of power plants, grid-connected feeders for distributed PV and marine power distribution systems. It can serve as primary protection or backup protection for distribution transformers and motors. It forms a complete set with UNITROL excitation systems, SACO16D1 alarm annunciators and DCS/SCADA. Complying with IEC61850 and CE certification, it supports protection logics for ring networks, radial networks and distributed generation grid-connected systems.

Brief Code Definition:

H=Complete assembled unit; B=IEC standard specification; F=Feeder application; D=Configuration including non-directional overcurrent, non-directional earth fault protection and on-line circuit breaker monitoring; the suffix NAA1BCN1XE defines power supply, I/O configuration, communication, housing, coating and optional accessories.

Mounting: 1/4×19-inch drawer plug-in type, flush panel mounting inside control cabinet.

2. Hardware & Electrical Specifications

2.1 Power Supply

  • Auxiliary supply: Universal wide-range AC80~265V / DC80~265V; customized DC24V low-voltage version available optionally
  • Typical power consumption: ≤8W with low-power flame-retardant design
  • Dielectric withstand: 2kV AC withstand test for 1 minute between analog/digital terminals and earth; galvanic isolation among internal circuits

2.2 Onboard I/O Configuration

表格
I/O Type Specification Application
AI Analog Input 3-phase CT input AC1A/5A, 3-phase PT input AC100V plus residual current & residual voltage inputs Collect three-phase and zero-sequence electrical values for protection sampling and energy metering
DI Digital Input 16 standard passive binary inputs DC220V/DC24V Collect circuit breaker position, spring charge status, disconnector status, local/remote selection, device fault and interlock signals
DO Relay Output 8 standard dry contact relays rated AC250V/8A with high-capacity output Protection tripping, closing output, fault alarm, auto-reclosure action and remote fault signal to DCS
RTD (standard for D version) 6-channel PT100 RTD inputs Temperature monitoring for cabinet cable terminals and circuit breaker contacts

2.3 Communication Interfaces (Standard for this model)

  • Dual 100Mbps copper Ethernet: IEC61850 MMS/GOOSE/9-2LE, supports PRP/HSR redundant network and IEEE1588 time synchronization
  • Isolated RS485: Modbus-RTU, DNP3.0, IEC60870-5-103 for connection with DCS, SACO16D1 alarm annunciator and REG670 protection relays
  • Front RS232 debug port: On-site parameter setting, fault oscillography download and logic programming via PCM600 software
  • Time synchronization: SNTP, IRIG-B code and PPS hard pulse synchronization

2.3 Dimension & Ambient Parameters

  • Dimension: W177mm × H177mm × D201mm (excluding wiring terminals); net weight ≈4.1kg
  • Ingress Protection: IP54 front panel with dustproof cover; IP20 inside cabinet
  • Ambient range: Operating -25℃~+70℃; Storage -40℃~+70℃; Humidity 5%~95% RH non-condensing
  • Standards: IEC60255, DNV marine certification, EMC compliance with IEC61000

3. Core Protection, Control & Measurement Functions

3.1 Full Set of Feeder Protection (D version: non-directional OC + non-directional EF + CB online monitoring)

  • Phase Fault Protection: Instantaneous overcurrent, definite time overcurrent, inverse-time overcurrent and thermal overload protection (long inverse-time characteristic)
  • Earth Fault Protection: Residual overcurrent, high-impedance earth fault detection and sensitive residual voltage protection for isolated neutral or arc-suppression coil grounded power grid
  • Voltage Protection: Overvoltage, undervoltage, PT fuse failure blocking, over/under frequency protection
  • Optional Functions: Arc Flash Detection (AFD), non-electrical tripping (gas alarm, overtemperature interlock), auto-reclosure with 1~4 adaptive shots with early/late acceleration logic
  • Blocking Logic: CT break protection blocking, trip circuit supervision and breaker failure remote tripping initiation

3.2 Control & Local Operation

Remote opening/closing of circuit breaker, local front-panel manual operation, spring charge supervision, operation counter and customizable five-prevention interlock logic.

Comprehensive electrical measurement: 3-phase U/I/P/Q/PF, active/reactive energy metering, sequence component and harmonic distortion monitoring.

3.3 Fault Recorder, Event Log & Self-diagnosis

  • Fault Recorder: Stores full waveform data no less than 10 cycles pre- and post-fault for local or remote download
  • Event Log: Min.1000 time-stamped SOE records with millisecond timestamp for protection operations, status changes and alarms
  • Periodic Self-test: Full hardware check at power-up plus cyclic online diagnosis; auto fault contact output for abnormal power, CPU or sampling to remote SCADA/DCS

4. Complete System Application Solution

  1. Feeder Panel Assembly: REF615 + SACO16D1 alarm annunciator + MCB + operating power supply to form secondary feeder cabinet
  2. Auxiliary Power for Generator Unit: Matched with UNITROL1000 excitation system and REG670 generator protection to build complete auxiliary feeder protection system
  3. Networking: Dual Ethernet via IEC61850 to substation automation host; RS485 link connected to DCS system