Description
Interface Configuration (Baseplate TP830)
Serial Ports:
COM3: RS-232C (with modem signals, for commissioning and service)
COM4: Isolated RS-232/485 (configurable as Modbus RTU master/slave)
Function Description
Redundant Control (Core Function)
Dual CPU hot standby redundancy, switchover time ≤ 10 ms
Redundancy coverage: CPU, CEX-Bus, communication interfaces and full S800 I/O system
Real-time Control
Boolean instruction execution speed: 0.03 μs
Minimum program cycle time: 1 ms
Clock synchronization: 1 ms accuracy among multiple controllers (CNCP protocol)
Communication Capability
Supports Modbus TCP/RTU, PROFIBUS DP, IEC 61850 and MMS
Connectable to over 200 S800 I/O stations, ideal for large-scale systems
Diagnosis & Maintenance
Hardware-level fault detection, redundant link diagnosis, event queue (3000 events per OPC client)
Supports online modification, hot-swappable I/O and remote maintenance
Application Scenarios
Kit Contents (3BSE082896R1)
2 × PM858 CPU modules
2 × TP830 baseplates
2 × TB807 bus terminators
1 × TK850 CEX-Bus extension cable
1 × TK851 RCU-Link redundancy synchronization cable
2 × 3.6V backup batteries






Reviews