Channel & Physical Interface Configuration
-
Channel Definition: 8 single-ended analog input channels, shared common ground reference, no inter-channel galvanic isolation; supports jumper-switched voltage/current input mode per channel
-
Matching Accessories: Exclusive pairing with cFP-CB-1 screw terminal blocks and cFP-BP-4/cFP-BP-8 backplanes; incompatible with legacy FP-TB series terminal bases
-
Status Indicators: 2 global green LEDs (POWER, READY) + 1 red over-range LED for out-of-bound signal alert
-
Hot Swap Performance: HotPnP powered hot swapping, no backplane bus crash or adjacent module data corruption during live plugging
-
Mechanical Parameters: Single-width compact cFP form factor, bare module weight 98 g, flame-retardant PC housing, IP20 indoor dust protection
Core Analog Input Electrical Parameters
-
ADC Architecture: 12-bit successive approximation register (SAR) ADC, different from delta-sigma ADC used on cFP-AI-111, faster response but lower noise filtering performance
-
Voltage Input Ranges: ±30 V, ±15 V, ±5 V, ±1 V, 0–30 V, 0–15 V, 0–5 V, 0–1 V and other 3 extended low-level ranges
-
Current Input Ranges: 0–20 mA, 4–20 mA, ±20 mA; fixed 100 Ω built-in shunt resistor for current sampling
-
Input Impedance: 1 MΩ parallel with 11 pF for voltage mode; 100 Ω fixed impedance for current mode
-
Synchronous Update Rate: 360 Hz simultaneous sampling for all 8 channels, no independent channel rate adjustment
Accuracy & Noise Rejection Specifications
-
Total Static Accuracy @25 ℃: ±(0.1% reading + 0.1% full scale), higher error than cFP-AI-111 for precision measurement
-
Temperature Drift: 45 ppm/℃ gain drift, 3.5 μV/℃ offset drift across full temperature range
-
CMRR & Crosstalk: >90 dB common-mode rejection at 50/60 Hz; channel-to-channel crosstalk <0.01% full scale
-
Input Overrange Tolerance: ±35 V continuous voltage overrange, ±25 mA continuous current overrange without hardware damage
-
Onboard Diagnostics: Open-circuit detection for 4–20 mA loops, automatic fault flag output for broken transmitter wiring
Isolation & Safety Compliance
-
Isolation Structure: Galvanic isolation between field analog side and backplane communication/power bus; no inter-channel isolation
-
Dielectric Withstand Index: 2,300 Vrms 5-second transient impulse withstand, 250 Vrms continuous CAT II field-to-backplane isolation
-
Explosive Environment Certification: UL/ATEX/IECEx certified for Class I Div 2 Groups A/B/C/D T4, Zone 2 non-sparking hazardous locations
-
Basic Safety Standards: IEC 61010-1, UL 61010-1, CSA C22.2 No.1010.1, Pollution Degree 2 indoor dry environment only
-
Altitude Derating: Isolation voltage reduced by 30% when operating above 2000 m altitude
Environmental & Shock-Vibration Reliability
-
Operating Temperature: -40 ℃ ~ 70 ℃ full-range rating with no parameter derating
-
Storage Temperature: -55 ℃ ~ 85 ℃, 10%–90% RH non-condensing humidity for transportation and storage
-
Random Vibration: 5 grms 10–500 Hz compliant with IEC 60068-2-64
-
Mechanical Shock: 50 g 3 ms half-sine operational shock, 30 g 11 ms transportation shock
-
EMC Grade: CE/FCC/C-Tick Class A industrial electromagnetic emission, compliant with EN 61326 immunity standards
cFP-AI-100 vs cFP-AI-111 Core Contrast
-
Channel Count: AI-100 = 8 channels; AI-111 = 16 channels (double density)
-
ADC Type: AI-100 SAR ADC (fast fixed sampling); AI-111 Delta-Sigma ADC (configurable noise filtering)
-
Signal Type: AI-100 voltage + current dual universal input; AI-111 only current input
-
Update Rate: AI-100 fixed 360 Hz; AI-111 configurable 1.23s~0.29s variable rate
Compatibility Matching List
-
Matching Backplanes: cFP-BP-4 (4-slot), cFP-BP-8 (8-slot) Compact FieldPoint backplanes
-
Matching Controllers: cFP-2120, cFP-2220 Ethernet remote FieldPoint controllers
-
Matching Terminal Blocks: cFP-CB-1 universal screw terminal block (non-isothermal, fully compatible)
-
Official Replacement Model: NI-9207 C-series 8-channel universal voltage/current analog input module
-
Official Status: Fully end-of-life, no official firmware updates or factory repair, only aftermarket tested inventory
Software Compatibility
-
Required Drivers: NI-FieldPoint legacy driver suite, NI-VISA underlying communication driver
-
Configuration Tools: NI MAX, FieldPoint standalone I/O configuration utility
-
Development Software: LabVIEW 2019 and earlier versions, LabWindows/CVI
-
Supported OS: Windows XP/7/10; no native Windows 11 driver, incompatible with LabVIEW 2021+ releases
Pros & Limitations
-
Pros: Dual voltage/current universal input without external signal conditioning, open-loop fault diagnosis for current loops, dedicated over-range alarm indicator, wider voltage input range than AI-111, low static power consumption, hazardous location certification, hot-swap maintenance
-
Limitations: Only 8 channels with lower density, fixed non-adjustable sampling rate, poorer high-frequency noise suppression than delta-sigma AI-111, no inter-channel isolation, discontinued official technical support
Official Product Images & Visual Reference
-
Front Panel Render: Standard grey cFP housing, extra red over-range LED besides dual global status LEDs
-
Assembly Photo: cFP-AI-100 paired with cFP-CB-1 installed on cFP-BP-8 backplane
-
AI-100 vs AI-111 Contrast: Identical exterior size, only front LED quantity and internal ADC circuit differ
-
Document Source: NI official user manual 370278A, unwatermarked factory original images