Description
Channel & Physical Interface Configuration
-
Channel Definition: 8 single-ended voltage output channels, shared common ground bus, no inter-channel galvanic isolation, all channels default power-on to 0 V to avoid actuator misstart
-
Matching Accessories: Exclusive pairing with cFP-CB-1 screw terminal blocks and cFP-BP-4/cFP-BP-8 backplanes; incompatible with legacy FP-TB series terminal bases
-
Status Indicators: 2 global green LEDs (POWER, READY) + 8 independent red channel overcurrent LEDs for per-channel fault localization
-
Hot Swap Performance: HotPnP powered hot swapping, no backplane communication downtime or adjacent module signal disturbance during live plugging
-
Mechanical Parameters: Single-width compact cFP form factor, bare module weight 115 g, flame-retardant PC housing, IP20 indoor dust protection
Core Analog Output Electrical Parameters
-
DAC Resolution: 12-bit monotonic DAC, 4096 discrete output levels, minimum resolution step 2.5 mV, guaranteed monotonicity across full temperature range
-
Output Voltage Range: Standard 0–10 V; extended over-range 0–10.2 V for calibrating transmitter span drift and long cable voltage drop
-
Current Drive Capacity: Default mode (no external power): ±1 mA per channel; Auxiliary power mode (15–30 VDC input): ±10 mA per channel
-
Slew Rate: 0.5 V/μs fast output response, suitable for dynamic valve closed-loop regulation
-
All-Channel Update Rate: 200 synchronous updates per second, fixed sampling period with no user-configurable adjustment
Accuracy & Temperature Drift Specifications
-
Offset Error @25 ℃: Typical 4 mV, maximum 14 mV across all channels
-
Gain Error @25 ℃: Typical 0.2% FS, maximum 0.4% FS full-scale deviation
-
Temperature Drift Coefficient: Offset drift 70 μV/℃, gain drift 20 ppm/℃, low drift for long-duration outdoor cabinet operation
-
Output Short-Circuit Tolerance: Continuous short-circuit protection to ground, automatic current limiting without permanent channel burnout
-
Output Impedance: <0.2 Ω low output impedance, minimizing signal attenuation for 50m shielded analog wiring
Overcurrent & Fault Protection Logic
-
Per-Channel Overcurrent Alarm: Independent red LED lights once channel current exceeds rated limit, fault latches until module power cycle reset
-
Input Overvoltage Protection: Auxiliary power port withstands -10 V ~ 20 V transient reverse voltage, preventing wiring polarity reversal damage
-
Fault Isolation: Single-channel overcurrent will not affect other 7 output channels, avoiding full-system control failure
-
Default Safe State: All outputs hold 0 V during backplane communication loss, meeting industrial fail-safe control requirements
Isolation & Safety Compliance
-
Isolation Structure: Galvanic isolation between field output side and backplane communication/power bus; zero inter-channel isolation
-
Dielectric Withstand Index: 2,300 Vrms 5-second transient impulse withstand, 250 Vrms continuous CAT II field-to-backplane isolation
-
Explosive Environment Certification: UL/ATEX/IECEx certified for Class I Div 2 Groups A/B/C/D T4, Zone 2 non-sparking hazardous locations
-
Basic Safety Standards: IEC 61010-1, UL 3121-1, CSA C22.2 No.1010.1, Pollution Degree 2 indoor dry environment only
-
Altitude Derating: Isolation voltage reduced by 30% when operating above 2000 m altitude
Environmental & Shock-Vibration Reliability
-
Operating Temperature: -40 ℃ ~ 70 ℃ full-range rating with no electrical parameter derating
-
Storage Temperature: -55 ℃ ~ 100 ℃, 10%–90% RH non-condensing humidity
-
Random Vibration: 5 grms 10–500 Hz compliant with IEC 60068-2-64
-
Mechanical Shock: 50 g 3 ms half-sine operational shock, 30 g 11 ms transportation shock
-
EMC Grade: CE/FCC/C-Tick Class A industrial electromagnetic emission, compliant with EN 61326 immunity standards, shielded wiring mandatory for EMC compliance
Compatibility Matching List
-
Matching Backplanes: cFP-BP-4 (4-slot), cFP-BP-8 (8-slot) Compact FieldPoint backplanes
-
Matching Controllers: cFP-2120, cFP-2220 Ethernet remote FieldPoint controllers
-
Matching Terminal Blocks: cFP-CB-1 universal screw terminal block, no isothermal terminal required
-
Official Replacement Model: NI-9263 C-series 4-channel 10V analog output module, NI-9264 for 8-channel migration
-
Official Status: Fully end-of-life, no official firmware updates or factory repair, only aftermarket tested inventory
Software Compatibility
-
Required Drivers: NI-FieldPoint legacy driver suite, NI-VISA underlying communication driver
-
Configuration Tools: NI MAX, FieldPoint standalone I/O configuration utility
-
Development Software: LabVIEW 2019 and earlier versions, LabWindows/CVI
-
Supported OS: Windows XP/7/10; no native Windows 11 driver, incompatible with LabVIEW 2021+ releases
Pros & Limitations
-
Pros: Dual-mode current drive adapting low-power analog actuators, 0.2V built-in over-range for field calibration, independent per-channel overcurrent indication, fail-safe 0V default state, wide extreme temperature tolerance, hazardous location certification, hot-swap online maintenance
-
Limitations: Voltage-only output without current analog output, limited 10mA maximum drive current, no inter-channel isolation, fixed non-adjustable update rate, discontinued official technical support
Official Product Images & Visual Reference
-
Front Panel Render: Standard grey cFP housing, 8 compact red overcurrent LEDs arranged on front panel alongside dual global indicators
-
Assembly Photo: cFP-AO-210 paired with cFP-CB-1 installed on cFP-BP-8 backplane
-
Module Side Marking: Printed auxiliary power pin definition for external 15-30VDC wiring
-
Document Source: NI official user manual 373347A, unwatermarked factory original images









Reviews