Description
ABB SACO16D1 16-Channel Digital Alarm Annunciator
1. Product Overview
Basic Information
- Product Name: 16-channel programmable digital alarm annunciator
- Product Series: SACO series site-specific alarm annunciators for power stations
- Mounting: Panel flush mounting inside control cabinet
- Application: Secondary alarm signal collection for thermal/hydro/gas turbine excitation systems, high & low voltage power distribution rooms and marine electrical systems
-
2. Electrical & Hardware Specifications
2.1 Power Supply
- Main auxiliary supply: Wide-range AC 80~265V / DC 80~265V (standard with SPGU240A1 power board); low voltage version DC 18~80V (SPGU48B2)
- Internal loop supply: Built-in isolated DC48V for powering field passive DI contacts with galvanic isolation between internal and external circuits
- Total power consumption: ≤18VA
- Dielectric strength: Withstands AC2000V/1min insulation test between terminals and earth
2.2 I/O Configuration
表格Interface Type Specification Application DI Digital Input 16-channel passive contact input; NO/NC configurable individually; channel delay adjustable 5ms~160s Acquire signals of protection operation, field breaker status, cooling system fault and unit abnormal alarms DO Relay Output 4-channel dry contact relay rated AC250V/5A: 2 common alarm outputs, 1 audible alarm output, 1 unit self-diagnosis fault output Control external buzzer, remote DCS alarm and fault interlock 2.3 Communication Interfaces
- SPA Bus (ABB proprietary protocol): Connect to REG670 protection relays, UNITROL excitation controllers and upper SCADA/DCS systems
- RS232 debug port: On-site parameter configuration, event log download and channel logic programming
2.4 Mechanical & Ambient Parameters
- Panel cutout dimension: W251mm × H142mm; unit depth: 229mm (excluding mounting frame)
- Ingress Protection: IP54 for front panel with transparent dust cover; IP20 inside cabinet
- Temperature: Operating -10℃~+55℃; Storage -40℃~+70℃
- Humidity: 5%~95% RH non-condensing, compliant with IEC60068 and DNV marine environmental standards
- Net weight: Approx.3.1kg
3. Core Functions
- First-out fault logic: 4-digit digital display locks the first triggered alarm channel, prioritizing the initial fault point under multiple fault conditions, standard design for power system application.
- 16 independent LED status lamps with 5 ISA/DIN compliant flashing modes: OFF in normal state, flashing during fault, steady ON after acknowledgement, OFF after reset.
- Periodic full hardware & software self-test; dedicated fault DO contact activates automatically upon power failure or internal malfunction.
- Event memory: Stores no less than 500 time-stamped alarm records for remote uploading via communication.
- Individual channel enable/disable and anti-chatter delay configurable to adapt to unstable field contact signals.






Reviews